The CircuitSolver® Sanitary Flush allows for higher water temperatures to flow through a domestic hot water system (DHWS) during a disinfecting process to protect against Legionella growth.
Unit of Measure

Specifications

Brands

N/A ThermOmegaTech®

Line Size

N/A 1/2 in

Closing Temperature

N/A 110 ºF43.3 ºC

Valve Options

N/A Standard

End Options

N/A ProPress® Ends

Thermometer Options

N/A Thermometer

Maximum Pressure

N/A 200 psig14 bar

Maximum Temperature

N/A 250 ºF121 ºC

Applications

N/A Sanitary

How it Works

How it Works

N/A The tamper-proof CSUSF uses two thermal actuators to control the flow of water through a branch/riser.

During standard operation of a DHWS, the first (low temperature) actuator balances the system. When the water temperature in the line reaches the set point of the actuator, the CircuitSolver® modulates to its closed position to keep the hot water at the fixtures. This forces the additional water on to the other branches maintaining a constantly balanced system.

When high temperatures are released into a DHWS during a thermal disinfection process, the low temperature actuator will begin to reopen, allowing the high temperature water to flow through the branch again.

When the water temperature reaches the set point of the second (high temperature) actuator, the CircuitSolver® modulates to its closed position again to keep the high temperature water at the fixtures.